https://doi.org/10.35290/ro.v4n3.2023.953
Diagnosis of the power quality in the welding warehouse of
the company CIAUTO Cia. Ltda.
Diagnóstico de la calidad de energía en la nave de soldadura de la
empresa CIAUTO Cia. Ltda
Date of receipt: 2023-05-29 Date of acceptance: 2023-07-14 Date of publication: 2023-10-10
Jaime Efraín Pérez López¹
Universidad Técnica de Cotopaxi, Ecuador
jaime.perez4296@utc.edu.ec
https://orcid.org/0009-0005-3993-9001
Franklin Hernán Vásquez Teneda²
Universidad Técnica de Cotopaxi, Ecuador
franklin.vasquez@utc.edu.ec
https://orcid.org/0000-0002-2442-4348
Carlos Iván Quinatoa Caiza³
Universidad Técnica de Cotopaxi, Ecuador
carlos.quinatoa7864@utc.edu.ec
https://orcid.org/0000-0001-6369-7480
Abstract
In this article a diagnosis of the power quality in the welding hall of the company CIAUTO
Cía. Ltda. is carried out, following the Ecuadorian regulation No. ARCERNNR - 002/20. The
electrical parameters are recorded with the FLUKE 435-II and analyzed according to the
quality of the product and the consumer. The results reveal that the power factor is below
0.92, indicating inefficient use of electrical energy. In the evaluation of the quality of the
product, it is observed that the voltage remains within the established limits, although it
decreases considerably during working hours, on the other hand, the Flicker does not meet the
standard, also the individual harmonic distortion specifically in the fifth harmonic 20% of
variables recorded exceed 5%, unlike the total harmonic voltage distortion (THD) that meets
the regulation. Likewise, an analysis of the quality in relation to the consumer is performed,
revealing alarming levels of current consumption that exceed the nominal levels of the 800
kVA transformer at 325 A, also 90% of individual current harmonics greatly exceed the limits
and the total demand distortion (TDD) has records of harmonics up to 80.04%. Finally, it is
determined that the power quality in the welding hall of CIAUTO Cía. Ltda. presents
deficiencies in power factor, Flicker and harmonic distortion. These results highlight the need
to take measures to improve energy efficiency and ensure power quality for both the product
and the consumer.
Keywords: electrical diagnostics, power quality, voltage, current, harmonics
Resumen
En este artículo se efectúa un diagnóstico de la calidad de energía en la nave de soldadura de
la empresa CIAUTO Cía. Ltda., siguiendo la regulación ecuatoriana No. ARCERNNR -
002/20. Los parámetros eléctricos se registran con el FLUKE 435-II y se analizan en función
a la calidad del producto y al consumidor. Los resultados revelan que el factor de potencia se
sitúa por debajo de 0.92, lo que indica una ineficiente utilización de la energía eléctrica. En la
evaluación de la calidad del producto, se observa que el voltaje se mantiene en los límites
establecidos, aunque disminuye considerablemente en el horario de trabajo, por otro lado, el
flicker no cumple la norma, también la distorsión armónica individual específicamente en el
quinto armónico el 20% de variables registradas superan el 5%, a diferencia de la distorsión
armónica total de voltaje (THD) que cumple la regulación. Asimismo, se realiza un análisis de
la calidad en relación al consumidor, revelando niveles alarmantes de consumo de corriente
que superan los niveles nominales del transformador de 800 kVA en 325 A, también el 90%
de armónicos de corriente individual exceden ampliamente los límites y la distorsión de
demanda total (TDD) tiene registros de armónicos de hasta el 80.04%. Finalmente, se
determina que la calidad de energía en la nave de soldadura de CIAUTO Cía. Ltda. presenta
deficiencias en el factor de potencia, flicker y distorsión armónica. Estos resultados resaltan la
necesidad de tomar medidas para mejorar la eficiencia energética y garantizar la calidad de
energía tanto para el producto como el consumidor.
Palabras clave: diagnóstico eléctrico, calidad de energía, voltaje, corriente, armónicos
Introduction
Electric power supply is widely used by a variety of industrial and domestic consumers
around the world (Popa, 2022). In the last decade, Ecuador has experienced a significant
increase in its population, which has driven the development of the Ecuadorian Electricity
System. This system plays a crucial role in ensuring the supply of energy to meet an ever-
growing demand (Abril et al., 2023). Power quality (PQ) analyzes the variety of
electromagnetic phenomena in electrical networks, in a facility is affected by the presence of
electrical disturbances that can affect the voltage, current or frequency that are generated in
the power plants, distribution system or user facilities (Cai et al., 2019). The use of devices
with non-linear loads such as: welding, furnaces, variable frequency drives (VFD), flexible
AC transmission (FACTS) and power electronic converters are the main cause of disturbances
in electric power systems (Khetarpal & Tripathi, 2020). Poor power quality causes incorrect
operation of the loads, or even damage that generates interruptions in the manufacturing
processes. It should be emphasized that the current equipment that makes up the electrical
system are more sensitive to electrical variations, for this reason, it is necessary to perform
periodic measurements of the PQ to reduce maintenance costs and extend the service time of
the equipment (Ojo et al., 2019; Polo et al., 2017).
The researchers Campaña et al. (2023) state that the increase in demand in the different power
electric systems (PES) has a negative impact on voltage stability, reliability and quality of
power supply. While Vitaliy et al. (2019) determined statistical characteristics of the power
quality indicators and distortion curves, Vizuete et al. (2019) analyzed the causes of low-
quality voltage supply based on voltage parameters, harmonics, voltage flicker, average
voltage and power factor. In the study, they determined that installing voltage regulators
improved energy efficiency in the analyzed company. The investigation of Karmaker et al.
=
2
= [
=
2
(2019) stated that the large number of electric vehicles charging stations that are integrated
into the electrical grid produce harmonics, voltage drop and increase and loss of power.
Power quality is determined based on the indicators evaluated at the point of delivery by the
distribution company, such as: voltage level, fast voltage disturbance (Flicker), harmonic
voltage distortion and voltage unbalance. On the other hand, it is important to highlight that
end users can negatively affect the electrical network by not complying with the regulatory
limits established for harmonic current distortion, which can alter the correct operation of the
electrical system (Espín, 2022).
The quality of the power system supply is subject to different evaluation standards to verify
amplitude and frequency variations (Martínez-Rodríguez et al., 2019). There are specialized
institutions that establish different procedures for auditing electrical quality, such as: IEEE,
IEC, EN-50160, EN-61000 (Martínez et al., 2022). In Ecuador, Regulation No. ARCERNNR
- 002/20 establishes PQ indicators and limits, in addition to defining procedures for
registration, measurement and evaluation, both for distribution utilities and users (Iñiguez-
Morán et al., 2023).
1.1 Regulation ARCERNNR-002/20
Quality attributes focused on the product and the consumer, established in section 5.1.1 and
5.2 of the regulation ARCERNNR 002/20, are described. Product quality is determined by
considering the voltage level, fast voltage disturbances (flicker) and harmonic voltage
distortion. The quality of the consumer is evaluated by measuring the harmonic current
distortion. The mathematical models related to the quality parameters are presented in
equations 1, 2, 3, 4 and 5.
∆𝑉
𝑘
= 𝑉𝑘−𝑉𝑛 𝑥100 [%] (1)
𝑉
𝑛
𝑃
𝑠𝑡
= 0.0314𝑃
0.1
+ 0.0525𝑃
1
+ 0.0657𝑃
3
+ 0.28𝑃
10
+ 0.08𝑃
50
(2)
𝑉
1 200
(𝑉
)
(3)
,𝑘 200
𝑖=1
,𝑖
𝑇𝐻𝐷
1
50 2
(4)
𝑘 𝑉
,1
=2
(𝑉
,𝑘
)
] 𝑥100 [%]
𝐼
1 200
(𝐼
)
(5)
𝑇𝐷𝐷
,𝑘
= [
1
200
50
𝑖=1
(𝐼
,𝑖
2
(6)
𝑘 𝐼
,1
=2
,𝑘
)
] 𝑥100 [%]
Where: ∆𝑉𝑘: supply voltage variation with respect to nominal voltage at point 𝑘; 𝑃𝑠𝑡: short
duration flicker severity index; 𝑉,𝑘: voltage harmonic at interval 𝑘 of 10 minutes; 𝑇𝐻𝐷𝑘:
total harmonic voltage distortion; 𝐼,𝑘: current harmonic at point 𝑘 every 10 minutes; 𝑇𝐷𝐷𝑘:
total current harmonics (ARCERNNR, 2023).
In the case of low voltage, the following requirements are established to ensure product
quality: the voltage must be within ±8% of the nominal voltage, the flicker must not exceed
unity, the maximum allowable limit for individual harmonic voltage distortion is 5%, and the
total harmonic voltage distortion must not exceed 8%.
On the other hand, in order to guarantee consumer quality, the corresponding limits are
presented in Table 1. It is important to highlight that, in the case of even harmonics, a limit
equivalent to 25% of the even value is established.
Table 1
Odd Current Harmonic Distortion
𝑰𝑪𝑪/𝑰𝑳
11
h<17
17
h<23
23
h<35
TDD
<20
2.0
1.5
0.6
5.0
20<50
3.5
2.5
1.0
8.0
50<100
4.5
4.0
1.5
12.0
100<1000
5.5
5.0
2.0
15.0
To obtain accurate parameters and analyze the power quality properly, it is necessary to
perform the measurement at the common point of coupling (PCC). The network analyzer used
must comply with IEC 61000-4-7 or IEC-61000-4-30.
The measurement must be carried out for at least 7 consecutive days, using 10-minute
sampling intervals. In order to comply with the established electrical quality parameters, 95%
of the records collected during this sampling period must comply with the limits defined in
this section.
1.2 Problem
In the vehicle assembly process at CIAUTO Cia. Ltda, the use of electrical equipment is
common, which involves a consumption of electrical energy that has a direct impact on the
quality of supply. The persistence of these electrical problems can cause uncontrolled
consequences in the future, directly affecting production and causing permanent damage to
the equipment.
In this context, the need arises to carry out a diagnosis of the electrical quality in the welding
shop of the company CIAUTO Cia. Ltda, where Great Wall vehicle chassis are assembled by
welding. Over the years, this brand has experienced an increase in sales, which has
necessitated a greater demand for electrical energy to assemble more vehicles.
For the diagnosis of electrical quality, this article follows the guidelines established in the
Ecuadorian Regulation No. ARCERNNR - 002/20. Also, the methodology used is described
and the results of the measurements of various electrical parameters are presented, such as
voltage level, flicker, voltage and current harmonic distortion, considering up to the thirtieth
harmonic component. The objective is to verify the power quality in relation to both the
product and the consumer in order to know the current situation of the different electrical
variables in the welding area.
In addition, the active power supplied to the equipment installed in the welding hall and the
power factor will be monitored to characterize the energy consumption. Finally, the detailed
analysis of the results obtained and the conclusions reached in the framework of this research
are presented.
Methodology
The study of power quality in the welding shop of CIAUTO Cía. Ltda. is carried out using the
Work Breakdown Structure (WBS) methodology. This methodology allows breaking down
projects into individual parts, which facilitates their management, thus establishing the limits
and scope of the project (Mañay et al., 2022).
The methodology is segmented into: direct observation of the low voltage system,
identification of the loads installed in the welding hall, measurement and analysis of the
power quality. Figure 1 shows the procedure of the study carried out.
Figure 1
Power Quality Study Procedure
2.1. Description of the industry
CIAUTO Cia. Ltda. is an Ecuadorian company located in the city of Ambato, in the province
of Tungurahua. In 2013, it began operations assembling Great Wall vehicles. It has body
welding lines for SUVs, pickup trucks and pickup buckets (Ciauto, 2023). Figure 2 shows the
location of the company.
Figure 2
Location CIAUTO, "The City of the Car"
Start
Check the equipment installed in the
welding hall
Establishing the common point of
coupling (PCC)
End
Present the results
Verify the electrical parameters received, based on
Regulation ARCERNNR - 002/20.
Installing the power analyzer
2.2 Welding hall
In the welding hall, the parts of the vehicles are joined by means of welding. In this hall, the
installed equipment is identified and information is collected.
The electric power supply to the welding hall comes from the distribution company EEASA,
through a medium voltage primary feeder of 60 Hz at 13800 V/33.36 A, which leads through
the protection cell to the 800 kVA transformer that lowers the voltage level to 380 V and
1215.47 A on the secondary side.
A total of 87 units are installed in the welding hall, of which 99.82% of the installed load is
composed of MIC welding (2 units), low frequency welding (40 units) and medium frequency
welding (20 units), with an installed capacity of 12,844.8 kW and 16,056 kVA. The
remaining percentage of the installed load (0.18%) is distributed among keyboards, water
pumps and fans (Espín, 2022). Figure 3 shows the single-line diagram of the welding area.
Figure 3
Simplified Single-Line Diagram
EEASA Network (13.8kV)
A/S
QM SM6-24kV
T-ECUATRAN
800kVA
13.800 ~ 380/400V
TDP-1
Bar duct
Pump room
M4 weld area Shineray welding area
Bar duct
Loose area Buckets Wingle welding area
2.3 Measuring instrument
The FLUKE 435 category II analyzer is a tool used to measure various electrical disturbances
that are essential for determining power quality. With the help of this analyzer, different
samples of active power, power factor, voltage, flicker, current and harmonics are collected in
the welding hall of the company CIAUTO Cia. Ltda. Figure 4 shows the equipment in
question.
Figure 4
FLUKE 435-II Quality Analyzer
2.4 Arrangement of the power quality analyzer
Main bar
Using the FLUKE 435 category II power quality analyzer as a support tool, electrical
parameters were recorded to verify compliance with the operating limits established for power
quality in the welding hall, in accordance with Regulation ARCERNNR - 002/20. The
analyzer was connected to the secondary side terminals of the 800 kVA transformer.
Monitoring was conducted under steady-state conditions, at a sampling frequency of 10
minutes, over a 7-day period from October 3 to October 9, 2022. Figure 5 shows the analyzer
in operation.
Figure 5
FLUKE 435-II Analyzer in Operation
Results
In this section, the results of nine factors recorded in the secondary of the 800 kVA
transformer of lines 1, 2 and 3 are presented. The factors analyzed include active power,
power factor, voltage, flicker, current and harmonics.
To verify compliance with energy quality standards, the ARCERNNR 002/20 regulation is
applied, which establishes that at least 95% of the records in each phase must be within the
admissible range. In this regard, a total of 607 data were collected to carry out the
corresponding evaluations.
3.1. Characterization of electricity demand
In order to evaluate the current energy demand in the welding hall of CIAUTO Cia. Ltda, a
monitoring of the active power and power factor was carried out. First, the maximum demand
of the company as a whole was verified, which was recorded at 770 kW.
Figure 6 shows the results of the maximum active power value for each line. Line 1 reaches a
maximum of 268 kW, line 2 reaches 288 kW and line 3 with 210.2 kW. In addition, the total
maximum consumption recorded is 451.2 kW.
Regarding the results presented, it should be noted that the maximum total power
consumption was recorded on October 7, 2022. In addition, it is observed that line 1 is
Sampling
Point
FLUKE 435 - II
generally overloaded, with the exception of October 6, 2022, where an overload is detected on
line 2.
Figure 6
Maximum Active Power
Power factor is a parameter that indicates how efficiently electrical energy is used to generate
useful work (Saucedo & Texis, 2008). A low power factor implies a loss of energy, which
translates into an additional cost in the electric bill. Power quality regulations establish that
the minimum value for the power factor is 0.92 (Hernández, 2021). The results of the power
factor studied are presented in Table 2.
Table 2
Power Factor Values
Variable analyzed
Maximum reading
Minimum reading
Power factor L1
0.87
0.61
Power factor L2
0.85
0.31
Power factor L3
0.88
0.53
Total power factor
0.86
0.67
It can be observed in Figure 7, that the power factor is under the limit of 0.92. The maximum
total power factor obtained was 0.86 and a minimum value of 0.67. In addition, a worrying
trend was identified on October 6, 2022 at 13:13, where minimum power factor values were
recorded on line 1 (0.61), line 2 (0.31) and line 3 (0.53). In conclusion, it can be determined
that the power factor is outside the allowed ranges established by the power quality
regulation.
Figure 7
Power Factor Trend
3.2 Power quality as a function of the product
According to ARCERNNR 002/20, product quality must comply with three main aspects:
voltage level, flicker and harmonic voltage distortion.
3.2.1. Voltage level
The welding vessel operates at voltage levels corresponding to the low voltage category,
which implies that the supply voltage must not exceed ± 8 % of the nominal voltage.
The nominal voltage between line and neutral is 219 V. According to the regulation, the
minimum allowed range is 201.52 V and the maximum range is 236.52 V. Figure 8 shows a
significant decrease in voltage during working hours. It is also concluded that voltage lines
L1, L2 and L3 are within the minimum and maximum limits established by regulation
ARCERNNR 002/20.
Figure 8
Line Voltage - Neutral
3.2.2. Rapid voltage disturbance (Flicker)
The power quality regulation ARCERNNR 002/20 establishes that the limit for Flicker at the
measurement point should not exceed unity. The results of the study are presented in Table 3.
Table 3
Flicker Readings
1
0,9
0,8
0,7
0,6
0,5
0,4
0,3
0,2
0,1
0
4:48:00 7:12:00 9:36:00
12:00:00
Tiempo
F. P. L3
14:24:00
16:48:00
19:12:00
F. P. L1
F. P. L2
F. P. Total
F. P. admitted
Maximum Power Factor: 0.88
6/10/2022 13:33:00
Minimum Power Factor: 0.31
6/10 2022 13:13:00
240
235
230
225
220
215
210
205
200
195
0:00:00 2:24:00 4:48:00 7:12:00 9:36:00 12:00:00 14:24:00 16:48:00 19:12:00 21:36:00 0:00:00
Time
Voltage L1-N Voltage L2-N Voltage L3-N Max. Limit Min. Limit
Minimum Voltage: 219.74 [V]
5/10/2022 11:03:00
Maximum Voltage: 236.63 [V]
6/10/2022 0:43:00
F. P.
[V]
Variable analyzed
Maximum reading
Minimum reading
Flicker L1
2,774
0,058
Flicker L2
3,5
0,06
Flicker L3
2,868
0,059
Figure 9 shows the trend of the Flicker readings, from which the following observations can
be made:
In line 1, 2 and 3, it was observed that 25%, 27% and 17% of the measurements, respectively,
are above unity.
In conclusion, although the largest number (>80%) of readings in lines 1, 2 and 3 are below
unity, it does not comply with ARCERNNR 002/20 regulation, which states that at least 95%
of the records must be below unity.
Figure 9
Flicker Trends
3.2.3. Harmonic voltage distortion
The ARCERNNR 002/20 regulation establishes that the maximum limit in low voltage for the
individual harmonic distortion factor must not exceed 5%, while for the total harmonic
voltage distortion factor (THD) it must not exceed 8%.
a) Individual harmonic voltage distortion
A comprehensive comparison was carried out using data obtained with the FLUKE 435-II
analyzer. In this study, measurements were made up to harmonic 30. Most of the harmonics
comply with the requirements established in the regulation, except for harmonic 5. In lines 1,
2 and 3, it was observed that 29%, 31% and 28% of the results, respectively, exceed the 5%
limit established for harmonic 5.
Figure 10 shows a general representation of the individual harmonic distortion. Harmonic 5 is
the most significant in the three lines analyzed with a value of 4.66% in line 1, while in line 2
it presents a value of 4.7% and in line 3 a value of 4.48% is observed.
Figure 10
Individual Harmonic Voltage Distortion
4
Maximum Pst.: 3.5
6/10/2022 14:53:00
3,5
3
2,5
2
1,5
1
0,5
0
0:00:00 2:24:00 4:48:00 7:12:00 9:36:00 12:00:00 14:24:00 16:48:00 19:12:00 21:36:00 0:00:00
Tiempo
Pst . L1 Pst. L2 Pst. L3 Max. Limit
Pst.
b) Total Harmonic Voltage Distortion (THDV)
The total harmonic distortion at low voltage should not exceed 8%. In Figure 11 it can be
observed that 100% of the analyzed data comply with the requirements established in the
ARCERNNR 002/20 regulation. It is important to highlight that the maximum value of the
total harmonic was recorded on October 4, 2022 at 11:13, reaching a percentage of 7.92%.
Figure 11
Total Harmonic Voltage Distortion
3.3. Energy quality according to the consumer
In this segment the line current in the welding hall is analyzed. It is important to note that the
800 kVA transformer has a rated current of 1215.47 A, while the busbars have a rated current
of 1500 A. In Figure 12, it can be clearly seen that the electrical consumption on October 6,
2022 exceeded the established nominal limits. The current of line 1 exceeded by 185 A, the
current of line 2 exceeded by 325 A, and line 3 registered an excess of 267 A with respect to
the rated current of the transformer. In addition, it is important to note that the current of line
2 exceeded the rated current of the busbars by 40 A.
These results indicate a worrying situation regarding load capacity and measures must be
taken to correct and avoid future electrical overloads in the welding hall.
9
Maximum THDV: 7.92 [%]
4/10/2022 11:13:00
8
7
6
5
4
3
2
1
0
0:00:00 2:24:00 4:48:00 7:12:00 9:36:00 12:00:00 14:24:00 16:48:00 19:12:00 21:36:00 0:00:00
Time
THD L1 THDV L2 THDV L3 THDV limit
[%]
Figure 12
Maximum Recorded Line Currents
3.3.1 Harmonic current distortion
In this part, the electrical quality in the welding hall is analyzed according to the consumer,
the individual harmonic distortion and the total harmonic distortion of current up to harmonic
30 are evaluated.
In order to establish the limits of current harmonics, it is necessary to perform mathematical
calculations according to IEEE519 (Jácome & Vargas, 2019). The fundamental parameter is
the impedance of the 800 kVA transformer, which is found to be 3.7%. This impedance is
used to determine the value of 𝐼𝐶𝐶, which is equal to 27.027A.
To calculate the value of 𝐼𝐿𝑝𝑢, the peak currents shown in Figure 12, in relation to the rated
current of the transformer, were used. This revealed the following values: 𝐼𝐿𝑝𝑢1=1.19,
𝐼𝐿𝑝𝑢2=1.26 and 𝐼𝐿𝑝𝑢3=1.219. Using these values, the ratio α was determined, which is
calculated as 𝐼𝐶𝐶 divided by 𝐼𝐿𝑝𝑢. The resulting values were 𝛼1=22.71, 𝛼2=21.34 and
𝛼
3
=22.17.
With the α results, the ratio 20<50 arranged in Table 1 was identified, where the current
harmonic limits are found. For individual harmonics in the range 3h<11, a maximum limit of
7% for odd harmonics and 1.75% for even harmonics is established. In the interval of
11h<17, the odd harmonics must comply with a limit of 3.5%, while the even harmonics
have a limit of 0.75%. Likewise, in the interval of 17h<23, the odd harmonics have a limit of
2.5%, while the even ones must comply with a limit of 0.625%. Finally, in the interval of
23h<35, the odd harmonics have a limit of 1%, while the even ones must comply with a
limit of 0.255%. In addition, a total harmonic current limit (TDD) of 8% is established.
a) Individual harmonic current distortion
An exhaustive comparison was carried out using the data obtained with the FLUKE 435-II
analyzer up to harmonic 30. After the comparison it was established that none of the harmonics
complies with the limits established by the ARCERNNR 002/20 regulation, in all the analyzed
cases 90% of the data exceed the normal limits.
Figure 13 shows a general representation of the individual harmonic distortion. Harmonic 5
stands out as the most significant harmonic in the three lines analyzed. In line 1, a value of
55.56% is recorded, while in line 2 it presents a value of 53.35%, and in line 3 a value of
56.77% is observed. In addition, 7 and 3 are identified as other important harmonics that
disturb the electrical system under study. These findings indicate the need to take corrective
measures to mitigate these harmonics and prevent the deterioration of the installations
Figure 13
Individual Current Harmonics
a) Total Demand Distortion (TDD)
The percentage of total harmonic current distortion must not exceed the limit of 8%
established by regulation ARCERNNR 002/20. However, in Figure 14 it can be observed that
in line 1, 93% of the data exceeds this limit, in line 2 it reaches 94%, and in line 3 91% of the
records are exceeded. It is important to highlight that the maximum value recorded for the
total harmonic occurred on October 3, 2022 at 19:13, reaching a percentage of 80.04% in line
3. These results indicate a high presence of harmonic distortion in the electrical system, which
requires actions to correct and reduce these levels, in compliance with established quality
standards.
Figure 14
Total Harmonic Voltage Distortion
Conclusions
The total electricity demand of CIAUTO Cia. Ltda., oscillates around 770 kW. Of this value,
the welding plant represents 58.5% of the demand, which is equivalent to a consumption of
451.2 kW.
Likewise, an analysis of consumption was carried out in the different lines L1, L2 and L3
with maximum peak records of 268 kW, 288 kW and 210.2 kW respectively. It is important
to highlight that line 1 presented overloads in general, with the exception of October 6, 2022,
when an overload was detected on line 2.
In relation to the power factor, a maximum value of 0.86 was obtained. It is worrisome to
highlight an alarming trend recorded on October 6, 2022 at 13:13, where lines L1, L2 and L3
showed a power factor of 0.61, 0.31, and 0.53 respectively. These results clearly indicate that
the power factor is below 0.92 established by the power quality regulation. Given this
situation, it is imperative to take immediate and corrective measures to improve energy
efficiency in order to avoid penalties and power supply problems.
As for power quality in terms of the product, aspects such as: voltage level, flicker and
harmonic voltage distortion were evaluated. According to the ARCERNNR 002/20
regulation, the admitted variation is 201.52 V to 236.52 V which is ± 8% of the nominal
voltage of 219 V between line and neutral of the supply to the welding hall. During the
working hours, a significant voltage decrease was observed. However, the voltage of L1, L2
and L3 remained within acceptable parameters and did not exceed ± 8% of the nominal
voltage.
When analyzing the Flicker at L1, L2 and L3, it was observed that 25%, 27% and 17%
respectively of the measurements exceed unity. This indicates that it does not comply with the
regulation that indicates that at least 95% of the records must be less than unity.
To analyze the individual harmonic distortion, it was taken up to harmonic 30, from which,
except for harmonic 5, they comply with the ARCERNNR 002/20 regulation. In harmonic 5,
29%, 31% and 28% in L1, L2 and L3 respectively exceed the 5% limit established in the
regulation. While, the total harmonic voltage distortion (THD) 100% of the data comply with
90
80
70
60
50
40
30
20
10
0
0:00:00 2:24:00 4:48:00 7:12:00 9:36:00
12:00:00 14:24:00 16:48:00 19:12:00 21:36:00 0:00:00
Time
TDD L1 TDD L2 TDD L3 TDD limit
Maximum TDD: 80.04 [%]
3/10/2022 19:13:00
[%]
the regulation. It is important to highlight that the maximum THD value was recorded on
October 4, 2022 at 11:13, reaching a percentage of 7.92%.
In relation to the power quality in relation to the consumer, the following were evaluated:
consumption current, individual current distortion and total demand distortion (TDD). In
relation to the consumption, the nominal current value of 1215.47 A of the 800 kVA
transformer was exceeded. On October 6, 2022, the current consumption in L1, L2 and L3
exceeded the nominal value of the transformer by 185 A, 325 A, and 267 A respectively. In
addition, it is important to note that the current of line 2 also exceeded the rated current of the
busbars by 40 A. These results indicate a worrying situation in terms of load capacity and
measures should be taken to correct and avoid future electrical overloads in the welding hall.
In the evaluation of the individual harmonic current distortion, harmonic 5 was the most
severe in the three lines analyzed with a distortion of 55.56%, 53.35% and 56.77%
respectively. In addition, harmonics 7 and 3 were identified as other important harmonics that
disturb the electrical system under study. These findings indicate the need to take corrective
measures to mitigate these harmonics.
In the total demand distortion (TDD), it was determined that in lines L1, L2 and L3 93%, 94%
and 91% of the records exceeded the 8% limit set by regulation ARCERNNR 002/20. It is
important to highlight that the maximum TDD value recorded occurred on October 3, 2022 at
19:13, reaching a distortion of 80.04% on line 3. These results indicate a high presence of
harmonic distortion in the electrical system, which requires actions to correct and reduce these
levels.
In general, it is concluded that it is necessary to take measures to improve power factor,
reduce flicker and control harmonic distortion. These improvements will contribute to ensure
the power quality of the product and the consumer.
References
Abril, V., Ramírez, J., y Lucio, M. (2023). Influencia de la altitud sobre el riesgo de falla del
aislamiento de líneas de transmisión de 500 kV considerando el comportamiento estadístico
de los sobrevoltajes. REVISTA ODIGOS, 4(1), 3153.
https://doi.org/10.35290/ro.v4n1.2023.774
ARCERNNR. (2023). Regulación Nro. ARCERNNR 002/20. In Resolución Nro.
ARCERNNR-003/2023. Agencia de Regulación y Control de Electricidad y Recursos
Naturales No Renovables. www.controlrecursosyenergia.gob.ec
Cai, K., Cao, W., Aarniovuori, L., Pang, H., Lin, Y., & Li, G. (2019). Classification of Power
Quality Disturbances Using Wigner-Ville Distribution and Deep Convolutional Neural
Networks. IEEE Access, 7, 119099119109. https://doi.org/10.1109/ACCESS.2019.2937193
Campaña, M., Masache, P., Inga, E., & Carrión, D. (2023). Voltage stability and electronic
compensation in electrical power systems using simulation models. Ingenius, 2023(29), 923.
https://doi.org/10.17163/ings.n29.2023.01
Ciauto. (2023). La Ciudad del Auto. In Ciauto. https://ciauto.ec/
Espín, M. (2022). Identificación de alternativas de mejora en la gestión de energía eléctrica
en el área de soldadura en la empresa Ciauto Cia. Ltda.-Ciudad del Auto ubicada en la
ciudad de Ambato, mediante el desarrollo de auditoría eléctrica [Tesis de Ingeniería,
Universidad Politécnica Salesiana].
https://dspace.ups.edu.ec/bitstream/123456789/21875/1/UPS%20-%20TTS601.pdf
Hernández, K. (2021). Diagnóstico y evaluación de las instalaciones eléctricas en la empresa
de servicios en tecnología y telecomunicaciones WODEN Ecuador S.A con criterios de
eficiencia energética [Tesis de Ingeniería, Escuela Politécnica Nacional].
https://bibdigital.epn.edu.ec/bitstream/15000/21616/1/CD%2011101.pdf
Iñiguez-Morán, V, Villa-ávila, E., Ochoa-Correa, D., Larco-Barros, C., & Sempertegui-
Álvarez, R. (2023). Study of the energy efficiency of an urban e-bike charged with a
standalone photovoltaic solar charging station and its compliance with the ecuadorian grid
code no. Arcernnr 002/20. Ingenius, 2023(29), 4657.
https://doi.org/10.17163/ings.n29.2023.04
Jácome, R., y Vargas, H. (2019). Análisis de calidad de energía eléctrica de la empresa
florícola AGRORAB CIA LTDA. Ubicada en el cantón pujilí [Tesis de Ingeniería, Universidad
Técnica de Cotopaxi]. http://repositorio.utc.edu.ec/jspui/bitstream/27000/5353/1/PI-
001331.pdf
Karmaker, A., Roy, S., & Ahmed, M. (2019). Analysis of the Impact of Electric Vehicle
Charging Station on Power Quality Issues. In Cox’sBazar (Ed.), 2019 International
Conference on Electrical, Computer and Communication Engineering (ECCE) (pp. 16).
IEEE. https://doi.org/10.1109/ECACE.2019.8679164
Khetarpal, P., & Tripathi, M.(2020). A critical and comprehensive review on power quality
disturbance detection and classification. In Sustainable Computing: Informatics and Systems
(28). Elsevier Inc. https://doi.org/10.1016/j.suscom.2020.100417
Mañay, E., Chiliquinga, M., Taco, H., & Moreno, M. (2022). Internet of things system for
ultraviolet index monitoring in the community of Chirinche Bajo. REVISTA ODIGOS, 3(2),
925. https://doi.org/10.35290/ro.v3n2.2022.595
Martínez, R., Castro, P., Arroyo, A., Manana, M., Galan, N., Moreno, F., Bustamante, S., &
Laso, A. (2022). Techniques to Locate the Origin of Power Quality Disturbances in a Power
System: A Review. In Sustainability,14(12), 7428. https://doi.org/10.3390/su14127428
Martínez-Rodríguez, G., Cruz-Isidro, B. de J., Garrido-Melendez, J., y Jiménez-Rivera, J.
(2019). Análisis de la calidad de energía eléctrica en una subestación de 300 kVA. Revista de
Operaciones Tecnologicas, 1220. https://doi.org/10.35429/jto.2019.11.3.12.20
Ojo, A., Awodele, K., & Sebitosi, A. (2019). Power Quality Monitoring and Assessment of a
Typical Commercial Building. 2019 IEEE AFRICON, 16.
https://doi.org/10.1109/AFRICON46755.2019.9133970
Polo, V., Peña, J., y Pacheco, L. (2017). Calidad de la energía eléctrica bajo la perspectiva de
los sistemas de puesta a tierra. Ciencia e Ingeniería, 38(2), 167176.
Popa, G. (2022). Electric Power Quality through Analysis and Experiment. In Energies,
15(21), 7947. https://doi.org/10.3390/en15217947
Saucedo, D., y Texis, J. (2008). Factores que afectan la calidad de la energía y su solución
[Tesis de Ingeniería, Instituto Politécnico Nacional].
https://tesis.ipn.mx/bitstream/handle/123456789/429/FINALsauicedomtz.pdf?sequence=1&is
All
Vitaliy, K., Nikolay, T., & Yevheniia, K. (2019). Evaluating the Effect of Electric Power
Quality upon the Efficiency of Electric Power Consumption. 2019 IEEE 2nd Ukraine
Conference on Electrical and Computer Engineering (UKRCON), 556561.
https://doi.org/10.1109/UKRCON.2019.8879841
Vizuete, A., Barbosa, G., Lema, E., Albán, M., Vargas, R., & Ruiz, L.(2019). Voltage Supply
Assessment Using Process Capability Concepts: A Case Study. IOP Conference Series:
Materials Science and Engineering, 559(1), 12011. https://doi.org/10.1088/1757-
899X/559/1/012011
Copyright (2023) © Jaime Efraín Pérez López, Franklin Hernán Vásquez Teneda y Carlos
Iván Quinatoa Caiza
Este texto está protegido bajo una licencia internacional Creative Commons 4.0.
Usted es libre para Compartircopiar y redistribuir el material en cualquier medio o formato
y Adaptar el documento remezclar, transformar y crear a partir del materialpara
cualquier propósito, incluso para fines comerciales, siempre que cumpla las condiciones de
Atribución. Usted debe dar crédito a la obra original de manera adecuada, proporcionar un
enlace a la licencia, e indicar si se han realizado cambios. Puede hacerlo en cualquier forma
razonable, pero no de forma tal que sugiera que tiene el apoyo del licenciante o lo recibe por
el uso que hace de la obra.
Resumen de licencia Texto completo de la licencia